เครื่องวัดอุณหภูมิความชื้น และความดัน สามารถรับสัญญาณได้ 3 input และมี output relay 2 output สั่งงานและดูผลผ่าน Internet
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| MODES OF COMMUNICATION | |
|---|---|
| Modbus TCP: | Modbus TCP protocol enables to read measured values and binary input states, set alarm limits, adjust the probe. |
| Telnet: | Port 9999 enables to set alarm limits (lower, upper limits, hysteresis for measured values and time delay), e-mail addresses, SNMP addresses, probe description, refresh of www pages (10s to 65535s), set storing interval to history (10s to 65535s), enable each communication channel. Capacity of the history memory is 100 sets of temperature, humidity, pressure + computed values. Password protection of this port is enabled. Automatic IP address assignment from DHCP server is also enabled. |
| WWW pages: | User selectable design of www pages enabling to display curve of measurement history and binary input states. User can design the look of www pages and temperature, humidity, pressure + computed values history.
Temperature, humidity, pressure in Roznov p.R., Czech Republic |
| SNMP: | It is possible to read actual values, alarm limits and binary input states. In case of alarm creation warning message (trap) is sent to addresses defined by the user (maximum three addresses). |
| SOAP: | Online transmitter enables to send actual measured data in the format of SOAP message to selected web server in preset interval 10-65535 s. |
Online transmitter enables to monitor measured values and binary input states. In case of exceeding of adjusted limits warning message can be sent to specified addresses.
There are the following options of alarm indication:
| ALARM INDICATION OPTIONS | |
|---|---|
| E-mail: | In case of alarm creation warning e-mail message is sent to addresses defined by the user (maximum three addresses) or via e-mail to SMS message. Basic SMTP autentization is supported. |
| SNMP: | In case of exceeding of adjusted temperature, humidity, pressure + computed value limits or binary input states alarm is activated and warning trap is sent to user specified IP addresses (maximum 3 addresses). |
| WWW pages: | In case of exceeding of adjusted temperature, humidity, pressure + computed value limits or binary input states active alarm is displayed on www page. |
| syslog: | Online transmitter enables to send text messages to selected syslog server after different events appear. E.g. after transmitter restart, alarm activation, communication error with SNTP, after firmware change, after alarm termination, after communication error with SOAP server. |
Synchronizing of time and record to www table and measured values history is enabled by SNTP via Internet.
| TECHNICAL PARAMETERS OF THE ONLINE SENSOR | |
|---|---|
| Maximum switching voltage, current, power of relay output: | 50V, 2A, 60VA |
| Audible alarm: | from built-in beeper - switchable |
| Operating relative humidity range: | 0 to 100% |
| Accuracy of relative humidity measurement: | ±2.5% relative humidity from 5 to 95% at 23°C |
| Temperature measurement accuracy: | ±0.4°C |
| Available temperature units: | degrees Celsius, Fahrenheit |
| Accuracy and range of dew point temperature: - for more details see graphs |
±1,5°C at ambient temperature T<25°C and RH>30% range -60 to +80 °C |
| Accuracy and range of absolute humidity output: | ±3g/m3 at ambient temperature T < 40°C range 0 to 400 g/m3 |
| Accuracy and range of specific humidity: | ±2g/kg at ambient temperature T < 35°C range 0 to 550 g/kg |
| Accuracy and range of mixing ratio: | ±2g/kg at ambient temperature T < 35°C range 0 to 995 g/kg |
| Accuracy and range of specific enthalpy: | ±3kJ/kg at ambient temperature T < 25°C range: 0 to 995 kJ/kg |
| Accuracy and range of barometric pressure output: | ± 1.3hPa at 23°C range: 600 to 1100hPa |
| Supported pressure units: | hPa, kPa, mbar, mmHg, inHg, inH2O, PSI, oz/in^2 |
| Temperature operating range of case with electronics: | -30 to +80°C |
| Temperature operating range of LCD display: | readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
| Range of RH sensor temperature compensation: | -30 to +105°C |
| Signal for binary inputs: | from voltage-less contact, open collector or two-state voltage signal. Inputs are not galvanically isolated. |
| Minimum pulse length at binary input: | 500 ms (shorter pulse may not be detected) |
| Voltage at open contact: | 3.3 V |
| Low voltage level: | 0 to +0.2 V |
| High voltage level: | +3.0 to +30V |
| Filtering ability of sensor cover: | 0.025mm - filter with stainless steel mesh |
| Protection: | IP30 electronics, IP40 sensors |
| LAN connection: | RJ-45 connector |
| Power: | 9 - 30 Vdc, maximum consumption 250mA. For power over Ethernet any PoE splitter is necessary e.g. DWL-P50 from D-Link company |
| Power connector: | co-axial, diameter 5.5 x 2.1 mm |
| Dimensions of the case: | 135 x 136 x 45 mm (W x H x D) |
| Warranty: | two years |